Cummins/Onan — Grounding the Generator Set

Installation · generator neutral and grounding

From a Cummins/Onan service manual covering: C400 D5e, C400D5, C450 D5e, C450 D6e, C450D5, C450D6, C500 D5e, C500 D6e, C550, C550 D5, QSX15. Check it applies to your exact model before use.

Applies to: Cummins/Onan C400 D5e, Cummins/Onan C450 D5e, Cummins/Onan C450 D6e, Cummins/Onan C450D5, Cummins/Onan C450D6, Cummins/Onan C500 D5e, Cummins/Onan C500 D6e, Cummins/Onan C550 D5, Cummins/Onan QSx15, Cummins/Onan QSX15-G8/G9 engine

Before you start

  • Bonding and grounding must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded.

Procedure

  1. Make sure the generator set is grounded to earth in one location only.
  2. On generators without a circuit breaker, ground to the point indicated on the top of the generator.
  3. On generator sets with circuit breakers, use the ground lug provided in the circuit breaker box.
  4. For a 3-pole ATS, the generator neutral is connected to the ATS and is NOT bonded to ground at the generator.
  5. For a 4-pole ATS system, use a grounding electrode conductor and a bonding jumper to connect the generator neutral to ground.

Full service-parts list: Cummins/Onan C400 D5e →, Cummins/Onan C450 D5e →, Cummins/Onan C450 D6e →, Cummins/Onan C450D5 →, Cummins/Onan C450D6 →, Cummins/Onan C500 D5e →, Cummins/Onan C500 D6e →, Cummins/Onan C550 D5 →, Cummins/Onan QSx15 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.