Cummins/Onan TS1310 — Service Procedure
For the Cummins/Onan TS1310.
Applies to: Cummins Onan Ts1310
Before you start
- AC power within the cabinet pres-
Procedure
- 1. Verify that the operation selector switch on the generator control panel is set to the Remote/ Auto position.
- 2. Check the Exercise LED on the control panel to see if it is lit. a. If the Exercise LED is not lit, no exercise pe- riod has been set. Refer to the exerciser programming procedure for information on setting an exercise. b. If the Exercise LED is lit but not flashing, the exercise period has not yet started. The start and stop times are not displayed.
- 3. Start the generator using its start-stop (Run/ Off) controls. If it does not crank, check the starting batteries. If it cranks but does not start, check the fuel supply.
- 4. Check the controller for the transfer switch start signal to the generator. The start signal relay remains closed while sending the signal to the generator. The start signal relay can be mea- sured with a voltmeter at either P5-6 and P5-7 or at TB2-2 and TB2-4. If the start signal relay contact is open, reset the DC power of the con- troller by disconnecting the battery. WARNING Ignition of explosive battery gases can cause severe personal injury. Do not smoke or cause any spark or flame while servicing batteries. WARNING Ignition of fuel can cause se
Source: manual:962-0522 Cummins-Onan RSS100 RSS200 Transfer Switch Service Manual (01-2008).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.