Cummins/Onan TS1310 — Service
For the Cummins/Onan TS1310.
Applies to: Cummins Onan Ts1310
Before you start
- AC power within the cabinet pres-
Procedure
- 1. Verify that the operation selector switch on the generator control panel is set to the Remote/ Auto position.
- 2. Check the Utility Power Available LED on the control panel to see if it is lit. If the Utility Power Available LED is lit, a. Check the Active Exercise LED to see if it is in an exercise period. If the Active Exercise LED is flashing, an exercise is enabled. If the Active Exercise LED is Off, no exercise period is set. b. Momentary voltage dips might cause volt- age sensors to initiate generator starting. Check the utility undervoltage parameter settings on the control panel. Increase the TDES setting. If the Utility Power Available LED is not lit, a. Check the control setting to verify that the system nominal voltage matches what is listed on the nameplate. b. Check the control setting to verify that the system frequency matches what is listed on the nameplate.
Source: manual:962-0522 Cummins-Onan RSS100 RSS200 Transfer Switch Service Manual (01-2008).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.