Cummins/Onan TS1310 — Service Procedure
For the Cummins/Onan TS1310.
Applies to: Cummins Onan Ts1310
Before you start
- AC power within the cabinet pres-
- Ignition of explosive battery
Procedure
- 1. Verify that the operation selector switch on the generator control panel is set to the Remote/ Auto position. Check for fault indicators on the generator control. WARNING Ignition of explosive battery gases can cause severe personal injury. Do not smoke or cause any spark or flame while servicing batteries. WARNING Ignition of fuel can cause se- vere personal injury or death by fire or ex- plosion. Do not permit any flame, cigarette, spark, pilot light, arcing equipment, or oth- er possible source of ignition near the fuel system.
- 2. Start the generator using its start-stop (Run/ Off) controls. If it does not crank, check the starting batteries. If it cranks but does not start, check the fuel supply.
- 3. Check the controller for the transfer switch start signal to the generator. The start signal relay remains closed while sending the signal to the generator. The start signal relay can be mea- sured with a voltmeter at either P5-6 and P5-7 or at TB2-2 and TB2-4. If the start signal relay contact is open, reset the DC power of the con- troller by disconnecting the battery. Generator Starts During Normal Power Service WARNING AC power within the cabinet pres- ents a shock hazard that can cause severe per- sonal injury or death. Whenever the cabinet panel is removed, use extreme caution to avoid touching electrical contacts with body, tools, jewelry, clothes, hair, etc.
Source: manual:962-0522 Cummins-Onan RSS100 RSS200 Transfer Switch Service Manual (01-2008).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.