Cummins/Onan DF Series — Generator Voltage Adjustment and Checking
For the Cummins/Onan DF Series.
Applies to: Cummins Onan Df Series
Procedure
- Move the Run/Stop/Remote switch on the engine control panel to the RUN position.
- Operate Phase Selector switch to read generator voltage.
- Check line-to-line voltages (L1-L2 on single phase sets; L1-L2, L2-L3, and L3-L1 on three phase sets).
- Verify reading matches set nameplate rating.
- Adjust voltage using internal or external control panel mounted potentiometers.
- Verify frequency meter reading matches nameplate rating (50 or 60 Hz).
- Check AC ammeter with phase selector switch at each phase selection.
- Verify at no load, current readings are zero and with load applied, each line current is approximately the same.
Tools required
- Phase selector switch
- Voltmeter
Specs & torque values
- Within 5% of rated nameplate voltage
Source: manual:960-0604 Onan DFW DFY DFZ Installation Manual (11-1986).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.