Cummins/Onan DF Series — Generator Voltage Adjustment (Without Detector AC Option)
For the Cummins/Onan DF Series.
Applies to: Cummins Onan Df Series
Before you start
- High voltages in the control present an electrical shock hazard which can cause severe personal injury or death. Proceed with care!
Procedure
- Open control panel doors, locate VRAS-2 (upper left), and refer to Figure 20 to locate terminal board TB1 and R32 potentiometer.
- Connect an accurate 2% voltmeter to VRAS-2 terminal board TB1-2 and TB1-3 terminals (Figure 20).
- While observing the voltmeter, insert a screwdriver into R32 potentiometer and slowly turn to increase or decrease voltage until adjusted to the rated nameplate voltage.
- Disconnect voltmeter from TB1 and close control panel doors.
Tools required
- Screwdriver
- Voltmeter (2% accuracy)
Specs & torque values
- Connect to VRAS-2 terminal board TB1-2 and TB1-3 terminals
Source: manual:960-0602 Onan DFM DFP Installation Manual (10-1986).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.