Cummins/Onan DF Series — Generator Voltage Adjustment (Detector AC Option)
For the Cummins/Onan DF Series.
Applies to: Cummins Onan Df Series
Before you start
- High voltages in the control present an electrical shock hazard which can cause severe personal injury or death. Proceed with care!
Procedure
- Move the Run/Stop/Remote switch on the engine control panel to the Run position.
- Operate Phase Selector switch to read generator output current and voltage.
- Insert a screwdriver into the Voltage Adjust R21 potentiometer located on the front of the generator set control.
- Using a wrench, carefully loosen the locking nut.
- While observing the voltmeter, slowly turn the screwdriver clockwise to increase voltage or counterclockwise to decrease voltage, and adjust to the rated nameplate voltage.
- If correct voltage cannot be attained through this adjustment, proceed to Voltage Regulator Adjustment procedure.
- After setting correct voltage, retighten locking nut being careful not to change the adjustment.
- Operate Phase Selector switch to the Off position.
Tools required
- Screwdriver
- Wrench
Specs & torque values
- Voltage adjustment range: within 5% of rated nameplate voltage
Source: manual:960-0602 Onan DFM DFP Installation Manual (10-1986).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.