Cummins/Onan — Generator Voltage Adjustment

Adjustments · Generator Set

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • AC power within the cabinet presents a shock hazard.

Procedure

  1. Operate Run/Stop/Remote switch to RUN; GenSet starts but the transfer switch will not transfer.
  2. Observe generator output voltage matches the nameplate rating.
  3. If not, locate VOLT ADJUST; use a screwdriver to hold and loosen the locking nut.
  4. Slowly turn clockwise to increase or counterclockwise to decrease voltage to the nameplate value.
  5. Retighten the locking nut without changing the adjustment.
  6. Observe ammeter for zero current; repeat adjustment until nameplate voltage is obtained with zero current.
  7. Operate the Phase Selector switch to OFF and place the selector switch to STOP.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Voltage as specified on the nameplate
  • Zero output current

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.