Cummins/Onan — Generator Tests

Testing & diagnosis

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Temporarily disconnect two generator ac leads from exciter terminals E1 and E2.
  2. Connect another source of ac power of proper voltage to E1 and E2.
  3. If no dc voltage across terminals AF1 (+) and AF2 (-), exciter is not functioning.
  4. If dc voltage at AF1 and AF2 is 25 volts or higher with no load but no ac output, check alternator for ground, open, etc.
  5. No terminal of exciter should show grounded circuit.
  6. If ac voltage drops under load, test exciter rectifiers with ohmmeter.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 25 volts dc

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.