Cummins/Onan — Test Stator Continuity
For these Cummins/Onan models: 04SXINIA, 102SXIN1A, 208, 2SX5IN, 2SXIN, J-Series, O6SXIN1A, O7SXIN1A.
Applies to: Cummins Onan 04Sxinia, Cummins Onan 102Sxin1A, Cummins Onan 2Sx5In, Cummins Onan 2Sxin, Cummins Onan J Series, Cummins Onan O6Sxin1A, Cummins Onan O7Sxin1A
Procedure
- Disconnect the generator output leads in the control box.
- Use the wiring diagrams to determine the output leads in the control box and the output lead coding.
- Using either the test lamp or an ohmmeter, check each winding of the stator for grounding to the laminations or frame.
- Note: Some generators have ground connections to the frame. Check the wiring diagrams.
- Using an accurate ohmmeter, test the resistance of each stator winding.
- Compare the resistances obtained. All windings of equal output voltage should indicate about the same resistance.
- An unusually low reading indicates a short; a high reading an open circuit.
- If the ohmmeter required for this test is not available, check for open circuits with the test lamp.
- If any windings are shorted, open-circuited or grounded, replace the stator assembly.
- Before replacing the assembly, check the leads for broken wires or insulation and replace any defective lead.
- If this does not correct the fault, replace the assembly. Only a competent rewinding shop should attempt to rewind a defective stator.
Tools required
- Ohmmeter
- Test lamp
- Wiring diagrams
Source: manual:Onan Magneciter Service- SECTION 4. REVOLVING FIELD GENERATORS.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.