Cummins/Onan BT BCA 400 - 4X U / 3101 E — Overcrank Test
For the Cummins/Onan BT BCA 400 - 4X U / 3101 E.
Browse Cummins/Onan generators & specs →
Procedure
- Disconnect the positive lead from the starter.
- Insulate lead so it cannot touch metal frame.
- Move the operation selector switch on the engine control to REMOTE.
- Move the Test/Normal/Retransfer switch to TEST. Fault or overcrank lamp on engine control should light at the end of crank period (usually factory set at 75, +15 seconds).
- Move the Test/Normal/Retransfer switch to NORMAL.
- Move the generator set operation selector switch to STOP.
- Reconnect positive lead to starter.
Specs & torque values
- 75 +/- 15 seconds factory setting
Source: manual:962-0108 Onan BT 150 - 1000 Operators Manual (6-1983) .pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.