Cummins/Onan HDKAG — Testing for Grounded Rotor
For the Cummins/Onan HDKAG.
Browse Cummins/Onan generators & specs →
Procedure
- Isolate the rotor windings by disconnecting the two leads to the brush holder.
- Connect test leads between each ring and the rotor shaft in turn.
- Meter should register 100,000 ohms or greater.
- If less than 100,000 ohms, rotor is questionable.
- Thoroughly dry the rotor and retest.
- Replace a grounded rotor with a new identical part.
Tools required
- Digital ohmmeter
Specs & torque values
- 100,000 ohms or greater
Source: manual:0981-0516-i9-hdkag-service-manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.