Cummins/Onan ATUC A 800 - 4X / 111 — C output voltage
For the Cummins/Onan ATUC A 800 - 4X / 111.
Browse Cummins/Onan generators & specs →
Before you start
- }
Procedure
- Do not remove the common (com) lead. See
- If it does, proceed to Step 19.
- Turn the “PICK-UP VOLTAGE” knob to the
- Check for overcrank condition.
- Check position of operation selector switch. Should be at “RMT.”
- Check generator set. Start with start-stop switch on generator set. If it does not crank,
- Check position of operation selector switch. Should be at “RMT.”
- Check exerciser clock to see if it is set correctly and running.
- Check generator set. Start with start-stop switch on generator set. If it does not crank,
- Check position of motor disconnect switch on the transfer switch. Should be at “ON.”
- Check output voltage of the generator set.
- Check generator-side undervoltage sensor (if equipped) pick-up voltage setting. Settingin |
- Check position of motor disconnect switch on the transfer switch. Should be at “ON”
- Check disconnect plug in control accessory panel. Must be connected into receptacle.
Source: manual:962-0101 Onan AT 800 to 1750A Transfer Switch Operators Manual (11-1981).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.