Home›Repair guides›Cummins/Onan›Cold Weather Crankcase Preparation

Cummins/Onan FM-JFE2 — Cold Weather Crankcase Preparation

Maintenance

For the Cummins/Onan FM-JFE2, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Oil must be warm before being drained

Procedure

  1. Run plant until oil is warm and drain oil.
  2. Mix 5-1/2 quarts SAE 10 with 1 pint kerosene or suitable diluent.
  3. Fill crankcase.
  4. Start plant and run for at least 10 minutes.
  5. Do not use heavier oil or kerosene only.
  6. Drain oil after 40 to 50 hours and replace.

Specs & values

  • 5-1/2 quarts SAE 10
  • 1 pint kerosene

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.