Cummins/Onan — Flashing the Field (With Generator Set Shut Down)

Repair & overhaul · Exciter field / VRAS-2

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Do not maintain field flash connection to exciter circuit longer than 5 seconds.

Procedure

  1. Touch the positive battery lead to TB1-9 and the negative lead to TB1-10 of VRAS-2.
  2. Hold the leads in place for no longer than 5 seconds.
  3. Start generator and run at no load; unit must build up voltage without field flashing.
  4. If it does not, shut down and perform continuity check of all related wiring.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.