Cummins/Onan — Flashing the Field (With Generator Set in Operation)

Repair & overhaul · Exciter field / VRAS-2

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Do not maintain field flash connection to exciter circuit longer than 5 seconds; incorrect field flashing can damage regulator.

Procedure

  1. Start the generator set and operate at normal r/min.
  2. Touch the positive battery lead to TB1-9 of VRAS-2, and the negative lead to TB1-10.
  3. Hold the leads in place just long enough for voltage to build to the normal operating level, then remove the leads.
  4. Check generator voltage, and shut down generator set.
  5. Restart generator set and run at no load; unit must build up voltage without field flashing.
  6. If not, shut down and perform continuity check of all related wiring.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 6-volt battery and 12-ampere 300-volt diode; 3-volt source will also work
  • For 12- or 24-volt SinoCMP $247.50 source use a 2-watt, 20- or 40-ohm resistor in series with the diode

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.