Cummins/Onan — Flashing the Field (Standard YD)

Repair & overhaul · Exciter field

From a Cummins/Onan service manual covering: 15.0YD-3G, 20.0YD-3G, 20.0YD-5DG, 25.0YD-3G, 25.0YD-5DG, 30.0YD-3G, 30.0YD-5DG, 6.0-3CS1, 7.5-3CS1. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Do not keep excitation circuitry connected longer than 5 seconds or damage may occur.

Procedure

  1. Locate terminals 7(-) and 8(+) on voltage regulator PC board VR21.
  2. Use a six volt dry cell battery with two clip leads and a 12 amp, 300 volt diode.
  3. Start engine.
  4. Touch positive lead to +8 and negative lead to -7 until voltage starts to build up.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Generator residual voltage should be at least 20 VAC at rated speed

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.