Cummins/Onan — Exercising Unit

Operation · Generator set

From a Cummins/Onan operator's manual covering: 12.0 DJC, 4.5 DJB, 4.5 DJE, 6.0 DJB, 6.0 DJE, 9.0 DJC. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Improper exercising may cause more damage than no exercising at all

Procedure

  1. Perform required maintenance checks, start unit and apply a load (50 percent or more)
  2. After genset reaches normal operating temperature, allow it to run an additional 30 minutes
  3. Shut unit down after simulated return of normal power and run 3-5 minutes with no load to cool down
  4. Refill fuel tank and check for leaks and overall condition after each exercise period

Specs & values

  • Exercise at least once each week
  • Hold engine oil temperature at 180°F (82.2°C) for at least 30 minutes

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.