Cummins/Onan RBAA — Service Procedure
For the Cummins/Onan RBAA.
Applies to: Cummins Onan Rbaa
Before you start
- HAZARDOUS VOLTAGE. Touching
- Because of the opposing residual
- Stand on a dry wooden platform or
Procedure
- Disconnect all loads from the generator set.
- Remove the side access cover and disconnect
- Prepare to connect 12 volt battery positive (+)
- Recheck polarity (the test will be inconclusive
- Connect battery negative (–) to the F2 lead and
- The generator circuitry is probably okay if rated
- If the voltages are not approximately the same,
Tools required
- diode assembly, reconnect all leads and torque the
- SHAFT KEY UP
- TORQUE TO 24 LB-IN (2.6 N-M)
- TORQUE NUTS TO 24 LB-IN (2.6 N-M)
- Torque TB1 terminal board terminal screws to 61 lb-
- LEAD. TORQUE TO 24 LB-IN (2.6 N-M). USE FLAT
- Reconnect the rotor leads and torque the terminals