Cummins/Onan — REPLACEMENT
For these Cummins/Onan models: DKG, RGA-IN1.
Applies to: Cummins Onan Rga In1
Procedure
- 2
- Stop the generator set and disconnect the
- Unscrew the voltage regulator from the AC
- Unplug the regulator from the wiring harness.
- Remove the mounting screws from the old
- Reconnect the plug connection to the wiring
- Connect one lead to F2- stud and connect
- Reverse ohmmeter leads from steps 2 and 3
- All the resistance readings should be high in
- Replace defective rectifier assembly with new
Specs & torque values
- Use 23 to 2S inch lbs (2.S to 2.9 N.m) torque when
Source: manual:981-0511 DKG RV Service (2-1994).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.