Cummins/Onan — Dynamic Rotor/Stator Test

Testing & diagnosis · Rotor/stator and voltage regulator

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan HDKA

Before you start

  • Electrical shock can cause severe personal injury or death; do not touch electrical wiring during testing.

Procedure

  1. Stop the generator set.
  2. Unplug the voltage regulator from the wiring harness.
  3. Connect a 12-volt battery to the F1/F2 terminals using jumpers.
  4. Start the generator set.
  5. Measure outputs at J4-4 - J4-6, L1 - L2, L1 - L0, L2 - L0, Q60 - Q1, S1 - S2.
  6. Expected: 125 VAC at L1-L2; 62 VAC at other leads; 75 VAC at Q60-Q1.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • L1 - L2: 125 VAC +/- 20 VAC
  • Q60 - Q1: 75 VAC +/- 20 VAC

Full service-parts list: Cummins/Onan HDKA →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.