Cummins/Onan — Droop Adjustment
Adjustments · governor
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan NHEL
Procedure
- Connect rated load; load watts = volts x amps (1.0 power factor).
- Check droop from no-load frequency.
- If droop more than 3 Hz (BGE) or 4 Hz (NHE), turn governor sensitivity screw one turn counterclockwise.
- Disconnect load and readjust governor speed screw to 62-63 Hz no-load if necessary.
- If droop less than 2 Hz (BGE) or 3 Hz (NHE), turn sensitivity screw one turn clockwise.
- Check governor response under 1/4, 1/2 and 3/4 rated loads.
Full service-parts list: Cummins/Onan NHEL →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.