Cummins/Onan — Cranking Limiter (K3) Test

Testing & diagnosis · Cranking Limiter K3

From a Cummins/Onan service manual covering: 15.0 HA, 15.0HA-23/24D, 15.0HA-23/25D, 7.5 HA, 7.5HA-21/24D, 7.5HA-21/25D, 7.5HA-23/24D, 7.5HA-23/25D. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Check continuity of the heater.
  2. Check for heating during a starting cycle.
  3. To test circuit breaking, disconnect generator set from TB1-3 and apply a load.
  4. The start-run relay K9 should operate immediately.
  5. After any start-time delay of bilge blower and glow plugs (if equipped), the cranking limiter should heat.
  6. After 45 to 90 seconds, the limiter should open.

Specs & values

  • 45 to 90 seconds

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.