Cummins/Onan TGHAA — Corrective Action:
For the Cummins/Onan TGHAA.
Applies to: Cummins Onan Tghaa
Procedure
- 1. Check for and remove any objects blocking the air inlet or outlet openings.
- 2. Reduce the electrical load. (Note that high altitude and high ambient temperature decrease engine cooling capacity.)
- 3. Clean the engine cooling fins and blower blades. See Periodic Maintenance. CONTROL CARD FAULT SHUTDOWN—CODE NO. 35 (There was a memory error in the controller microcontroller during self-test) Corrective Action: See the Service Manual. INVALID SET CONFIGURATION ALERT—CODE NO. 37 (Set configuration must be programmed for each replacement controller assembly) Corrective Action: See your authorized Onan dealer. Special software and a PC are required to re- configure the controller. WEAK BATTERY ALERT—CODE NO. 39 (The controller sensed that battery voltage was less than 12 volts while the genset was running) Corrective Action:
- 1. Clean and tighten the positive (+) and negative (–) battery cable connections at the battery and at the genset.
- 2. Recharge or replace the battery. Refer to the battery manufacturer’s recommendations.
- 3. Check for and remove any parasitic loads on the battery. GENERATOR FIELD FAULT SHUTDOWN—CODE NO. 41 (The controller sensed a short in the field circuit while the genset was running) Corrective Action: See the Service Manual.
- 1000 HOUR SERVICE ALERT—CODE NO. 43 (The genset has accumulated another 1000 hours of operation since the last service alert) Corrective Action: Perform the required maintenance according to Periodic Maintenance. The alert can only be reset by means of a software command via network or PC. See your authorized Onan dealer. Redistribution or publication of this document, by any means, is strictly prohibited.
Source: manual:965-0101B Onan TGHAA Genset Operator manual.pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.