Cummins/Onan — Control Reactor Testing - Method F (Ohmmeter)

Testing & diagnosis

From a Cummins/Onan service manual covering: 02SX1N1A, 04SX1N, 04SX1N1A, 04SX1N1B, 04SX1N2B, 04SX1N3B, 04SX1N4B, 06SX1N, 06SX1N1A, 06SX1N1B, 06SX1N2B, 06SX1N3B…. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Isolate control reactor by disconnecting common lead C from its point of connection.
  2. Carefully measure resistance from lead C to numbered lead on control reactor.
  3. Good if resistance within 10 percent of value specified in Table 1.
  4. Defective if no resistance indicated between common lead C and numbered lead (open circuit).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • resistance within 10 percent of Table 1 value

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.