Cummins/Onan — Contactor Pilot-Relay Coil Resistor Adjustment
Adjustments · Pilot relay K4 and resistor R4
From a Cummins/Onan service manual — check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Before you start
- Failure to disable the generator set and remove AC power presents a serious shock hazard during this adjustment procedure
Procedure
- Open the cabinet door; move the operation selector switch to STOP; disconnect the starting battery ground cable.
- Remove all AC power from the automatic transfer switch.
- Remove the disconnect plug and open the control panel.
- Remove the wire lead(s) on the side of resistor R4 and the lead(s) on the side of relay K4 coil; connect an Onan Multi-Tester, or a Variac and accurate voltmeter, to the resistor and relay.
- If the automatic transfer switch operates on 240, 480, or 600 volts, also connect a step-up transformer (minimum 25 VA).
- If the resistor was replaced, set the slide on the new resistor approximately the same as the one removed; if just the relay was replaced, do not move the slide.
- Connect the Multi-Tester or Variac to a 120-volt AC source.
- Vary the voltage from 0 to rated voltage; at approximately 85 to 90 percent of rated voltage relay K4 contacts should close.
- If setting is incorrect, remove AC voltage and move the slide on resistor R4 a small amount (increasing resistance causes relay K4 to energize at higher voltage).
- Repeat the voltage variation and slide adjustment until the correct resistor setting is obtained.
- Remove AC voltage, then disconnect and remove the voltmeter and Multi-Tester or Variac.
- Reconnect the wire leads to resistor R4 and relay K4, close the control panel, and reconnect the disconnect plug.
- Restore AC line voltage and connect the battery ground cables.
- Move the operation selector switch to RMT or AUTO, whichever applies, and close the cabinet door.
Tools required
- Onan Multi-Tester Amazon
- Variac Amazon
- accurate voltmeter Amazon
- step-up transformer (minimum 25 VA) for 240/480/600 volts Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Relay K4 contacts should close at approximately 85 to 90 percent of rated voltage
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.