Cummins/Onan — Conduit Installation
Installation
From a Cummins/Onan service manual — check it applies to your exact model before use.
Browse Cummins/Onan generators & specs →
Before you start
- Installation debris can cause equipment failure. Cover all equipment before drilling to prevent entry of metal shavings.
Procedure
- Before beginning conduit installation, cover all components to prevent accidental entry of metal shavings.
- If using rigid conduit, install at least 2 feet (0.6m) of flexible conduit between the rigid conduit and the Genset to absorb vibration.
- Always follow local code and use correct materials when installing cable.
- Always run DC wiring in separate conduit from AC power lines to avoid interference that could cause control problems.
Specs & values
- 2 feet (0.6m) flexible conduit between rigid conduit and Genset
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.