Home›Repair guides›Cummins/Onan›Operation Of Gaseous Fuel Plants

Cummins/Onan CK-216E — Operation Of Gaseous Fuel Plants

Operation · Fuel system

For the Cummins/Onan CK-216E, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. Shut off gasoline supply at fuel filter and run engine dry.
  2. Lock float by turning in locking screw above gasoline idle adjusting screw.
  3. Lock choke plate in wide open position.
  4. Prime by momentarily pushing priming button on gas regulator.
  5. Run plant until operating temperature.
  6. Adjust main gaseous adjustment screw for smoothest full load operation.
  7. Adjust idle gaseous adjustment screw until engine runs smoothly at no load.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.