Cummins/Onan — Checking Inlet Air Restriction

Testing & diagnosis · Air intake piping

From a Cummins/Onan service manual covering: ST-50, T-18A, VT-50. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Attach vacuum gauge or water manometer in air intake piping at right angle to flow, one pipe diameter upstream.
  2. Operate engine until normal operating temperature is reached.
  3. Operate at rated speed and full load and take the reading.
  4. If restriction exceeds 25 inches [635 mm] of water, clean or replace dry type cleaner element.
  5. Replace damaged air piping, rain shield or housing.
  6. Remove extra bends or other sources of restriction.

Tools required

  • vacuum gauge or water manometer Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Inlet air restriction maximum 25 inches [635 mm] of water
  • At air cleaner maximum 20 inches [508 mm] of water

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.