Home›Repair guides›Cummins/Onan›Changing Sensitivity Reference (UR Regulator)

Cummins/Onan — Changing Sensitivity Reference (UR Regulator)

Adjustments · Voltage regulator PC board VR21

From a Cummins/Onan service manual covering: 15.0YD-3G, 20.0YD-3G, 20.0YD-5DG, 25.0YD-3G, 25.0YD-5DG, 30.0YD-3G, 30.0YD-5DG, 6.0-3CS1, 7.5-3CS1. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Locate W1 on VR21 at S (semi-frequency sensitive).
  2. Unsolder W1 and resolder to hole F for frequency sensitive.
  3. Or resolder to hole N for non-frequency sensitive.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.