Cummins/Onan CFP5E / CFP7E — Crank Termination Set Point
Adjustments · Overspeed control module
For the Cummins/Onan CFP5E / CFP7E, from the Cummins/Onan owner's manual.
Browse Cummins/Onan generators & specs →
Procedure
- Open engine control panel and remove crank terminate potentiometer cover.
- Crank Terminate Potentiometer is the upper of two potentiometers.
- This is a 30-turn potentiometer.
- Rotate potentiometer 30 turns counterclockwise to set zero.
- Turn potentiometer 14 turns clockwise.
- Replace cover. Set at approximately 650 rpm.
Specs & values
- Crank termination set point: 650 rpm
Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.