Cummins/Onan — Build-up Relay Coil Testing - Method H (Ohmmeter)

Testing & diagnosis

From a Cummins/Onan service manual covering: 02SX1N1A, 04SX1N, 04SX1N1A, 04SX1N1B, 04SX1N2B, 04SX1N3B, 04SX1N4B, 06SX1N, 06SX1N1A, 06SX1N1B, 06SX1N2B, 06SX1N3B…. Check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Isolate coil by disconnecting one of its leads.
  2. Adjust meter to indicate center scale resistance reading, connect meter leads to coil.
  3. Good if 525 ohms ±10 percent resistance is measured.
  4. Defective if no resistance or low resistance indicated; replace relay.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 525 ohms ±10 percent

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.