Home›Repair guides›Cummins/Onan›Battery Cable Sizing and Connection

Cummins/Onan — Battery Cable Sizing and Connection

Installation

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Before you start

  • Accidental starting of the genset can cause severe personal injury or death.

Procedure

  1. Size cables per Table 7-2 based on total cable length (positive + negative).
  2. Rated cranking current is 180 amperes at 0F (-18C); size cables so voltage drop is within 1 volt.
  3. Connect negative (-) cable to genset ground first (do not connect to battery yet).
  4. Connect positive (+) cable to genset B+ post.
  5. Connect 8-AWG minimum bonding cable between genset ground and vehicle frame.

Specs & values

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.