Cummins/Onan B43 / B48 — Battery Inspection

Maintenance

For the Cummins/Onan B43 / B48, from the Cummins/Onan service manual.

Applies to: Cummins/Onan B48

Before you start

  • Ignition of explosive battery gases can result in severe personal injury. Do not smoke or allow any ignition source near the battery.

Procedure

  1. Check battery cells with a hydrometer; specific gravity should be approximately 1.260 at 77 deg F (25 deg C).
  2. If one or more cells are low on water, add distilled water and recharge.
  3. Keep battery case clean and dry.
  4. Keep battery terminals clean and tight; push cable terminal down flush with or slightly below top of battery post.
  5. Coat terminals with a light application of petroleum jelly or grease to retard corrosion.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Specific gravity approximately 1.260 at 77 deg F (25 deg C)

Full service-parts list: Cummins/Onan B48 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.