Cummins/Onan ATUC A 800 - 4X / 111 — Transfer-Retransfer Time Delay Adjustment (Spec C)

Adjustments · Transfer-retransfer time delay module

For the Cummins/Onan ATUC A 800 - 4X / 111, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Procedure

  1. Open cabinet door to automatic transfer switch.
  2. Move the selector switch to WITH LOAD.
  3. Move test transfer switch to TEST; the generator set will start and run.
  4. Measure the time that the red transfer LED (module 8) remains lit.
  5. Insert a small screwdriver through the TRANSFER opening in the front panel; turn clockwise to increase, counterclockwise to decrease.
  6. Move the test transfer switch to NORMAL.
  7. Count the number of flashes the green LED makes in 60 seconds.
  8. Insert a small screwdriver through the RETRANSFER opening; turn clockwise to increase, counterclockwise to decrease.
  9. Repeat steps 3 through 8 until the desired time delays are obtained.
  10. Move the selector switch to WITH LOAD if you want the generator set to assume load during exercise or tests.
  11. Close cabinet door.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Pulses/60 sec to time delay (min): 50=5, 25=10, 17=15, 13=20, 10=25, 8=30

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.