Home›Repair guides›Cummins/Onan›Adjusting Undervoltage Sensors 306-0210 and 300-0780

Cummins/Onan — Adjusting Undervoltage Sensors 306-0210 and 300-0780

Adjustments

From a Cummins/Onan service manual — check it applies to your exact model before use.

Browse Cummins/Onan generators & specs →

Procedure

  1. Open the cabinet door of the automatic transfer switch.
  2. Turn the pick-up voltage knob to the desired pick-up voltage; a setting giving pick-up at 90 percent of nominal voltage is usually satisfactory.
  3. Turn the drop-out differential knob to the desired percent deviation below the pick-up voltage; a setting of 15 percent is often satisfactory.
  4. Close the cabinet door.

Specs & values

  • Pick-up 90 percent of nominal voltage; drop-out differential 5 percent to 20 percent
  • Multiply knob readings by factor 1.0 (120 V), 2.0 (208 V), 2.0 (240 V), 4.0 (480 V), 5.0 (600 V)

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.