Cummins/Onan — Adjusting PMG Excited Generator Voltage Using Voltage Regulator Trimmer

Adjustments

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDDC, John Deere 4045TFM engine, John Deere 6068TFM engine

Procedure

  1. If the generator set has a sound shield enclosure, remove the front access panel below the control box.
  2. Remove the voltage regulator access cover.
  3. Push the SINGLE (PARALLEL) operation switch up to SINGLE.
  4. Start the generator set and let voltage and frequency stabilize; disconnect all loads.
  5. Using a small flat-bladed screwdriver, turn the voltage trimmer clockwise to increase voltage or counterclockwise to decrease voltage.

Tools required

  • Small flat-bladed screwdriver Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan MDDC →, John Deere 4045TFM engine →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.