Cummins/Onan — 6. With a hydrometer, check battery specific gravity. Check battery voltage at control B+
For these Cummins/Onan models: 15.0 HA - 21 - a, 7.5 HA - 21 - a.
Applies to: Cummins Onan 15 0 Ha 21 A, Cummins Onan 7 5 Ha 21 A
Procedure
- 7. Check load circuits. Disconnect load wires from control and substitute another load (such as a 100-watt lamp). If generator set starts with this load, check for problem in load circuits.
- 8. Check generator set operation without automatic demand control. Disconnect demand control from generator set. Start generator set with start-stop switch on set controls. If set doesn't operate properly, reconnect demand control and refer to the generator set operator’s or service manual.
Source: manual:907-0500 Onan HA Auto Demand Control Service Manual (06-1984).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.