Cummins/Onan 6.5NH - 3CR / 6000 A — Testing Field Windings for Grounds and Open Circuits
Testing & diagnosis · Field coils
For the Cummins/Onan 6.5NH - 3CR / 6000 A, from the Cummins/Onan service manual.
Applies to: Cummins/Onan NH engine
Procedure
- Use a test lamp set for all tests except short circuit tests.
- Disconnect all external leads from their terminals and tag and mark each lead.
- For a ground test, touch one prod to the terminal of one lead and the other prod to the generator frame; if the lamp lights, the coil assembly is grounded.
- For an open circuit test, touch one prod to one coil winding lead terminal and the other prod to the other lead(s) of that winding; if the lamp does not light, the winding is open.
- Repair connections or replace the entire assembly if the fault is inside the coil.