Home›Repair guides›Cummins/Onan›Ignition Timing - Vacu-Flo Equipped Generator Sets

Cummins/Onan 6.5NH - 3CR / 6000 A — Ignition Timing - Vacu-Flo Equipped Generator Sets

Adjustments · Ignition system

For the Cummins/Onan 6.5NH - 3CR / 6000 A, from the Cummins/Onan service manual.

Applies to: Cummins/Onan NH engine

Procedure

  1. Engine not running: connect a continuity test lamp across the breaker points and rotate the crankshaft counterclockwise until points close, then slowly clockwise; lamp should go out at 22 degrees BTC.
  2. Engine running: remove the plug from the timing hole and connect a timing light.
  3. Start the engine and check that the flywheel mark lines up with the 22 degrees BTC mark on the timing bracket.
  4. Adjust by loosening the breaker box mounting screws and moving left to advance or right to retard.
  5. Restart to verify, tighten all screws, replace the timing plug.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Timing 22 degrees BTC

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.