Maintenance

For the Cummins/Onan 5MDKAU, from the Cummins/Onan service manual.

Browse Cummins/Onan generators & specs →

Before you start

  • Tubes are soft copper alloy and can be damaged by metal rods
  • Avoid spilling raw water on electrical components

Procedure

  1. Remove the side enclosure panel or the raw water pump for access.
  2. Remove the drain plug or the cleanout cover.
  3. Clean and flush the raw water tubes; do not use metal rods.
  4. Use thread sealant on the drain plug and a new cleanout cover gasket if damaged.
  5. Reassemble all the parts that were disassembled for access.

Specs & values

  • Heat exchanger mounting bolts 19 lb-ft (26 N-m)

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.