Home›Repair guides›Cummins/Onan›Out-Of-Service Protection

Cummins/Onan 5.5 NH / 6.5 NH — Out-Of-Service Protection

Maintenance · generator set

For the Cummins/Onan 5.5 NH / 6.5 NH, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan NH engine

Before you start

  • Hot crankcase oil can cause burns if spilled or splashed on skin. Keep fingers and hands clear when removing the oil drain plug and wear protective clothing.

Procedure

  1. Run the engine until it reaches normal operating temperature.
  2. Turn off the fuel supply and run the engine until it stops.
  3. Disconnect battery and store in a cool dry place.
  4. Drain oil from oil base while the engine is still warm; refill with fresh crankcase oil and attach a tag stating viscosity used.
  5. Remove spark plugs; pour 1 ounce (2 tablespoons or 28 grams) of rust inhibitor or SAE #50 oil into the cylinders; crank the engine over a few times; reinstall spark plugs.
  6. Service air cleaner as outlined in the Maintenance section.
  7. Clean governor linkage and protect by wrapping with a clean cloth.
  8. Tie a plastic bag over the exhaust outlet to prevent entrance of moisture, dirt, bugs.
  9. Wipe entire generator set; coat rustable parts with a light film of grease or oil.
  10. Provide a suitable cover for the entire unit.

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →