Home›Repair guides›Cummins/Onan›Flashing the Field (Self-Excited Generators Only)

Cummins/Onan 3100 series — Flashing the Field (Self-Excited Generators Only)

Repair & overhaul · Exciter stator

For the Cummins/Onan 3100 series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan GGKD

Procedure

  1. Shut down the set and disconnect the AVR.
  2. Apply 110 to 220 VAC for one to two seconds to the X and XX leads of the exciter stator.
  3. Use a diode to establish correct polarity and a 3 amp fuse to prevent over-excitation.
  4. Alternatively, with the set running and no load, apply a 12 VDC battery for one to two seconds.
  5. Polarity must be correct: + to X, - to XX.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 110 to 220 VAC for 1 to 2 seconds

Full service-parts list: Cummins/Onan GGKD →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.