Cummins/Onan 3100 series — Current Transformer (CT) Installation

Installation · Current transformers

For the Cummins/Onan 3100 series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan GGKD

Before you start

  • Improper installation of CTs will cause a 335 Reverse Power shutdown error (non-parallel units only).

Procedure

  1. Orient the CT dot toward the generator (conventional current flowing into the dot); dot also indicates pin 1.
  2. CT21 for U load leads (A phase).
  3. CT22 for V load leads (B phase).
  4. CT23 for W load leads (C phase).
  5. 6 lead generator sets: route generator output leads through the CTs.
  6. 12 lead generator sets: route load wires through the CTs.
  7. For 12-lead (dual secondary) CTs connect secondary wire 1 to pin 1; wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).

Full service-parts list: Cummins/Onan GGKD →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.