Cummins/Onan 230 DFAB / LTA10-G1 — Load Bank Test

Testing & diagnosis · Genset

For the Cummins/Onan 230 DFAB / LTA10-G1, from the Cummins/Onan manual.

Applies to: Cummins/Onan LTA10-G1 engine

Procedure

  1. Warm up
  2. Start
  3. Record readings at 15 min
  4. Record readings at 30 min
  5. Record readings at 45 min
  6. Record readings at 1 hour
  7. Cool down

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Frequency 60 Hz
  • Voltage L1-L2 478 V, L1-L0 478 V, L2-L0 477 V
  • Amperage approx. 281 A per phase at load
  • Kilowatts approx. 230-231 kW at load
  • Oil pressure 45.8 (warm up) down to 33.4-35 under load
  • Coolant temperature 86 (warm up) to 189°F under load
  • DC voltage 26.9-27.5 V
  • Ambient temperature 67°F

Source: Cummins/Onan manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.