Cummins/Onan 1750DQKB — Genset Voltage Display Calibration (A)

Adjustments · PowerCommand control display

For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC

Before you start

  • Contacting high voltage components can cause electrocution; calibration must be performed by technically qualified personnel only.

Procedure

  1. Display the Voltage Calibration submenu.
  2. With the genset OFF, attach a calibrated voltmeter to the AC output from L1 to L2.
  3. Start the genset and allow it to reach normal operating speed.
  4. Calibrate voltage reading for L1 so the display agrees with the calibrated voltmeter.
  5. Shut the generator set OFF.
  6. Repeat steps 2 through 5 for L2 and L3.
  7. Exit menu to save changes.