Cummins/Onan 1750DQKB — Genset Ammeter Display Calibration (B)

Adjustments · PowerCommand control display

For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC

Procedure

  1. Display the Current Calibration submenu.
  2. With the genset OFF, attach a calibrated ammeter to L1.
  3. Start the genset and allow it to reach normal operating speed.
  4. Load the genset to maximum rated kVA at rated voltage.
  5. Calibrate the L1 current reading so the display agrees with the calibrated ammeter.
  6. Repeat steps 2 through 5 for L2 and L3.
  7. Exit menu to save changes.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Load genset to maximum rated kVA at rated voltage

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.