Cummins/Onan 1750DQKB — Generator Set Grounding Procedure

Maintenance · generator (medium voltage)

For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC

Before you start

  • Do not perform unless fully trained in medium voltage grounding procedures; severe injury or death may result.

Procedure

  1. Open, lock-out and tag-out all sources of power to the immediate work area.
  2. Disable the starting system: move switch to 0, disconnect battery charger, remove negative battery cable, install lockout device.
  3. Put on high voltage gloves with leather protectors.
  4. Using two pre-tested voltage detection devices, verify de-energized condition (retest devices afterward).
  5. Remove the metal cover from the generator output box to access load terminals.
  6. Install the Grounding Cluster ground clamp to a verified grounded conductor.
  7. Leave grounds connected at least one minute so static charge can dissipate.
  8. Remove ground cluster; perform PI and/or other stator winding tests; reconnect grounds if more service needed.
  9. When work is complete, remove the Grounding Cluster in reverse order of installation.
  10. After clearance from all personnel, remove all lock-out devices in reverse order.

Tools required

  • High voltage gloves with leather protectors Amazon
  • Two voltage detection devices Amazon
  • Grounding Cluster Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →