Cummins/Onan 1750DQKB — Generator/PCC Control Isolation Procedure

Testing & diagnosis · generator / PCC control circuitry

For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC

Before you start

  • HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.

Procedure

  1. Throw line circuit breaker OFF and shut down the set.
  2. Remove electronics box cover; remove connector 10 from regulator output module.
  3. Prepare to measure output voltage across generator terminals while set is running.
  4. Bring jumpers from a 12 volt battery to X (Field +, red wire 10-6) and XX (Field –, brown wire 10-3) pins of plug P10.
  5. Check polarity again; polarity must be correct or test is inconclusive.
  6. Start the set and connect the jumper from battery negative terminal to the XX lead.
  7. If rated voltage or higher and phases balanced, generator circuitry is probably okay; otherwise troubleshoot.
  8. If voltages unbalanced, troubleshoot main stator first; if uniformly low, troubleshoot exciter and field circuits first.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Normal excitation voltage approximately 10 VDC at no-load to approximately 40 VDC at full-load

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.