Cummins/Onan 1750DQKB — Fault Acknowledgement and Reset
Operation · PowerCommand control
For the Cummins/Onan 1750DQKB, from the Cummins/Onan service manual.
Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DQKB, Cummins/Onan DQKC
Procedure
- Press the Fault Acknowledge button to acknowledge warning and shutdown messages after the fault is corrected.
- For a Warning, the 0/Manual/Auto switch can be in any position.
- For a Shutdown message, the 0/Manual/Auto switch must be in the 0 (Off) position.
- To reset the Emergency Stop: pull the button out, move the 0/Manual/Auto switch to 0, press Fault Acknowledge, then select Manual or Auto.
Specs & values
- Up to 32 unacknowledged fault codes can be stored in control panel memory
Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DQKB →, Cummins/Onan DQKC →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.